ATTENTION: It has come to our note that a counterfeit website 'WWW.AKABISHI.COM' pretending as sister concern of MITSUBISHI ELECTRIC INDIA PVT LTD, displaying and retailing our registered Brand product 'AKABISHI' unauthorizedly through this fake website with purpose to defraud the customers. We would like to inform all GENERAL PUBLIC that MITSUBISHI ELECTRIC INDIA PVT LTD has no sister concern in INDIA and 'AKABISHI' a product of Mitsubishi Electric India is sold through our Authorized Channel Partners on PAN India basis, details of which is available on our registered website www.Mitsubishielectric.in or www.in.mitsubishielectric.com. We have no relations with WWW.AKABISHI.COM, hence if any customer may buy any type of AKABISHI product from this counterfeit website, Company will not be responsible for the product, payment and any kind of support services. Kindly purchase Aircon products Mitsubishi Electric and AKABISHI from our Authorized Channel Partner only.: BE VIGILANT
Total Capacity / Model Name

Technical Specifications

Model Name PUMY-CP100VKM PUMY-CP125VKM PUMY-CP140VKM
Power Source 1-phase 220-230-240 V, 50 Hz; 1-phase 220 V, 60 Hz
Cooling Capacity(Nominal) kW 11.20 14.00 15.50
Btu 38200 47800 52900
  Power Input kW 2.80 3.84 4.70
  Current Input A 12.99-12.42-11.90, 12.99 17.81-17.04-16.33, 17.81 21.80-20.85-19.98, 21.80
  EER kW/kW 4.00 3.65 3.30
Temp. range of cooling Indoor W.B. 15 to 24°C (59 to 75°F) 15 to 24°C (59 to 75°F) 15 to 24°C (59 to 75°F)
Outdoor D.B. 10 to 52°C (50 to 126°F) 10 to 52°C (50 to 126°F) 10 to 52°C (50 to 126°F)
Indoor unit connectable Total capacity 50 to 130% of outdoor unit capacity
Model/Quantity CITY MULTI 15-125/7 15-140/10 15-140/12
Sound pressure level *2
(measured in anechoic room)
dB(A) 52/- 53/- 54/-
Refrigerant piping diameter Liquid pipe mm(in.) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas pipe mm(in.) 15.88(5/8) 15.88(5/8) 15.88(5/8)
FAN Airflow rate m3/min 78.8
L/s 1313
cfm 2782
Type x Quantity   Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Motor Output kW 0.20 x 1
Compressor Type x Quantity Twin rotary hermetic compressor × 1
Starting Method Inverter
Motor Output kW 2.2 2.7 3.0
External Dimension HxWxD mm 981x1050x330(+25) 981x1050x330(+25) 981x1050x330(+25)
in. 38-5/8 × 41-3/8 × 13 (+1) 38-5/8 × 41-3/8 × 13 (+1) 38-5/8 × 41-3/8 × 13 (+1)
 Protection devices High pressure protection High pressure switch

Inverter circuit
(COMP./FAN)

Overcurrent detection, Overheat detection (Heat Sink thermistor)
Compressor Compressor thermistor, Overcurrent detection
Fan motor Overheating, Voltage protection
Refrigerant Type x original charge   R410A 2.9kg
Net weight kg/lbs 86(190) *4 86(190) *4 86(190) *4
External finish Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1 Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1 Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
Heat Exchanger Micro Slit Fin and Copper tube Micro Slit Fin and Copper tube Micro Slit Fin and Copper tube
Optional parts Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
  • *1 Nominal conditions
  •   Indoor Outdoor Pipe length Level difference
    Cooling 27ºC DB/19ºC WB
    (81ºF DB/66ºF WB)
    35ºC DB (95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.)
  • *2 Cooling mode/Heating mode.
  • *3 External static option is available(30Pa/3.1mmH2O.)
  • *4 87 (192), for PUMY-CP100/125/140VKM.TH-BS. 88 (195), for PUMY-CP100/125/140YKM.TH-BS.
  • *Nominal conditions *1 are subject to ISO 15042.
  • *Due to continuing improvement, above specification may be subject to change without notice.
  • *This unit cannot be connected with the PFFY-YM-E or PFFY-YMH-E.