ATTENTION: It has come to our note that a counterfeit website 'WWW.AKABISHI.COM' pretending as sister concern of MITSUBISHI ELECTRIC INDIA PVT LTD, displaying and retailing our registered Brand product 'AKABISHI' unauthorizedly through this fake website with purpose to defraud the customers. We would like to inform all GENERAL PUBLIC that MITSUBISHI ELECTRIC INDIA PVT LTD has no sister concern in INDIA and 'AKABISHI' a product of Mitsubishi Electric India is sold through our Authorized Channel Partners on PAN India basis, details of which is available on our registered website www.Mitsubishielectric.in or www.in.mitsubishielectric.com. We have no relations with WWW.AKABISHI.COM, hence if any customer may buy any type of AKABISHI product from this counterfeit website, Company will not be responsible for the product, payment and any kind of support services. Kindly purchase Aircon products Mitsubishi Electric and AKABISHI from our Authorized Channel Partner only.: BE VIGILANT

Technical Specifications

Model PFFY-P200YM PFFY-P250YM PFFY-P200YMH PFFY-P250YMH PFFY-P400YM PFFY-P500YM
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity (Nominal) *1 kW 22.4 28.0 22.4 28.0 45.0 56.0
*1 BTU/h 76,400 95,500 76,400 95,500 153,500 191,100
*2 Power input kW 0.490/0.680 1.05/1.26 1.00/1.41 1.31/1.41 2.86/3.79 3.94/5.30
*2 Current input (380-400-415 V) A 0.97-0.98-0.99/ 1.24-1.23-1.22 1.74-1.83-1.88/ 2.06-2.05-2.04 1.82-1.85-1.87/ 2.37-2.37-2.37 2.14-2.18-2.20/ 2.18-2.18-2.18 5.23-5.25-5.33/ 6.16-6.18-6.26 7.66-7.68-7.76/ 8.49-8.51-8.58
Heating capacity (Nominal) *3 kW 25.0 31.5 25.0 31.5 50.0 63.0
*3 BTU/h 85,300 107,500 85,300 107,500 170,600 215,000
*2 Power input kW 0.490/0.680 1.05/1.26 1.00/1.41 1.31/1.41 2.86/3.79 3.94/5.30
*2 Current input (380-400-415 V) A 0.97-0.98-0.99/ 1.24-1.23-1.22 1.74-1.83-1.88/ 2.06-2.05-2.04 1.82-1.85-1.87/ 2.37-2.37-2.37 2.14-2.18-2.20/ 2.18-2.18-2.18 5.23-5.25-5.33/ 6.16-6.18-6.26 7.66-7.68-7.76/ 8.49-8.51-8.58
External finish Galvanized steel plate (with polyester coating)
External dimension H x W x D mm 1,665 x 1,200 x 500 1,665 x 1,200 x 500 1,465 x 1,200 x 500 1,465 x 1,200 x 500 1,800 x 1,860 x 650 1,800 x 1,860 x 650
in. 65-9/16 x 47-1/4 x 19-11/16 65-9/16 x 47-1/4 x 19-11/16 57-11/16 x 47-1/4 x 19-11/16 57-11/16 x 47-1/4 x 19-11/16 70-7/8 x 73-1/4 x 25-5/8 70-7/8 x 73-1/4 x 25-5/8
Net weight kg (lbs) 157 (347) 158 (349) 138 (305) 139 (307) 310 (684) 362 (799)
Heat exchanger Cross fin (Aluminum fin and copper tube)
Fan Type x Quantity Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2 Sirocco fan x 2
External static press. (380 V) Pa <0> <0> <180>/<200> <180>/<210> <210>/<390> <290>/<510>
mmH2O <0.0> <0.0> <18.4>/<20.4> <18.4>/<21.4> <21.4>/<39.8> <29.6>/<52.0>
Motor Type 3-phase induction motor
Motor output kW 0.400 0.500 0.770 0.770 3.700 5.500
Driving mechanism Direct-driven by motor Belt driving
Air flow rate   (High-Low) (High)
m3/min 65.0-59.0/69.0-60.0 77.0-56.0/72.0-50.0 65.0 72.0 150.0 200.0
L/s 1,083-983/1,150-1,000 1,283-933/1,200-833 1,083 1,200 2,500 3,333
cfm 2,295-2,083/2,436-2,119 2,719-1,977/2,542-1,766 2,295 2,542 5,297 7,062
Sound pressure level (measured in anechoic room) (380 V)*2   (High-Low) (High)
dB (A) 58-56/60-56 63-60/62-60 58/60 60/61 68/69 69/69
Air filter PP honeycomb fabric.
Refrigerant piping diameter Liquid (R410A) mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed 9.52 (3/8) Brazed 9.52 (3/8) Brazed 12.7 (1/2) Brazed 15.88 (5/8) Brazed
Gas (R410A) mm (in.) 22.22 (7/8) Brazed 22.22 (7/8) Brazed 22.22 (7/8) Brazed 22.22 (7/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Field drain pipe size in. Rc 1 Rc 1 Rc 1 Rc 1 Rc 1-1/4 Rc 1-1/4

Notes:
*1  Nominal cooling conditions
  Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
  Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
*2  The values are measured at the factory setting of external static pressure.
*3  Nominal heating conditions
  Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
  Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
*4  Long period operation in a high temperature and humidity atmosphere (dew point of 23°C or more) may cause condensation to form in the indoor unit.
*5  In case of this type of unit is connected, the maximum connected indoor unit capacity to one outdoor unit have to be less than or equal to 100%.
*6  This unit cannot be connected to R2 or WR2-Series. (PFFY-P400, P500YM-E only)
*7  This unit cannot be connected to PUMY-Series.

* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.

 