Air Conditioning Systems

Ceiling Suspended

ATTENTION: It has come to our note that a counterfeit website 'WWW.AKABISHI.COM' pretending as sister concern of MITSUBISHI ELECTRIC INDIA PVT LTD, displaying and retailing our registered Brand product 'AKABISHI' unauthorizedly through this fake website with purpose to defraud the customers. We would like to inform all GENERAL PUBLIC that MITSUBISHI ELECTRIC INDIA PVT LTD has no sister concern in INDIA and 'AKABISHI' a product of Mitsubishi Electric India is sold through our Authorized Channel Partners on PAN India basis, details of which is available on our registered website www.Mitsubishielectric.in or www.in.mitsubishielectric.com. We have no relations with WWW.AKABISHI.COM, hence if any customer may buy any type of AKABISHI product from this counterfeit website, Company will not be responsible for the product, payment and any kind of support services. Kindly purchase Aircon products Mitsubishi Electric and AKABISHI from our Authorized Channel Partner only.: BE VIGILANT

Technical Specifications

Model PCFY-P40VKM PCFY-P63VKM PCFY-P100VKM PCFY-P125VKM
Power source 1-phase 220-240V 50Hz/1-phase 220V 60Hz
Cooling capacity kW*1 4.5 7.1 11.2 14.0
BTU/h*1 15400 24200 38200 47800
Heating capacity kW*1 5.0 8.0 12.5 16.0
BTU/h*1 17100 27300 42700 54600
Power
consumption
Cooling kW 0.04 0.05 0.09 0.11
Heating kW 0.04 0.05 0.09 0.11
Dimension
H x W x D
mm 230x960x680 230x1280x680 230x1600x680
In 9-1/16x37-13/16x26-3/4 9-1/16x50-3/8x26-3/4 9-1/16x63x26-3/4
Current Cooling A 0.28 0.33 0.65 0.76
Heating A 0.28 0.33 0.65 0.76
External finish (Munsell No.) 6.4Y 8.9/ 0.4
Net Weight kg(lbs) 24(53) 32(71) 36(79) 38(84)
Heat exchanger Cross fin (Aluminium fin and copper tube)
Fan Type x Quantity Sirocco fan x 2 Sirocco fan x 3 Sirocco fan x 4
Airflow rate
(Low-Mid2-Mid1-Hi) *2
cfm 353-388-424-459 494-530-565-636 742-847-918-989 742-847-953-1095
External static pressure Pa 0
Motor Type DC motor
Output kW 0.090 0.095 0.160
Air filter PP Honeycomb(long life)
Refrigerant
pipe diammeter
Gas
(Flare)
mm(in) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Liquid
(Flare)
mm(in) 6.35(1/4) 9.52(3/8)
Field drain pipe diameter mm(in) O.D. 26(1)
Sound pressure level
(Low-Mid2-Mid1-Hi) *2 *3
dB(A) 29-32-34-36 31-33-35-37 36-38-41-43 36-39-42-44
  • *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition. Cooling Indoor : 27°C(80.6°F)DB/19°C(66.2°F)WB, Outdoor 35°C(95°F)DB Heating Indoor : 20°C(68°F)DB, Outdoor 7°C(44.6°F)DB/6°C(42.8°F)WB
  • *2 Airflw rate/Sound pressure level are shown in (low-middle 2-middle 1-high).
  • *3 It is measured in anechoic room.